U4 — Daikin

Ichki va tashqi blok orasida ma’lumot uzatish nosoz

Ma’nosi
Ichki va tashqi blok orasida ma’lumot uzatish nosoz
Model seriyasi
Daikin umumiy jadvali: RA, SkyAir, VRV, PA, Heat Reclaim Ventilator
Manba
Simple Self-Diagnosis by Malfunction Code, After Sales Service Division (SM-TS3) · sahifa 5

«U4 Malfunction of transmission between indoor and outdoor unit Short circuit in indoor-outdoor or outdoor-outdoor transmission wiring (F1 / F2), or wrong wiring Outdoor unit power supply is OFF System address does not match»

Ma’no ishlab chiqaruvchi hujjatidan tarjima qilingan; asl matn manbada.

O‘zingiz tekshirsa bo‘ladigan narsalar

  1. Tashqi blokka elektr kelayotganini tekshiring: ba’zi tizimlarda u alohida avtomatdan ta’minlanadi.
  2. 5 daqiqaga elektrdan uzib, qayta yoqing.
  3. Yaqinda elektr yoki ta’mir ishlari bo‘lgan bo‘lsa, buni arizaga yozing — ulanish kabeli tekshiriladi.

⚠ Elektr qismlarini ochmang: platalar, kondensatorlar va kabellar o‘chirilgandan keyin ham kuchlanish ostida bo‘lishi mumkin. Bu ustaning ishi.

Shu kod bilan ariza qoldirish →

Shu brendning boshqa kodlari — Daikin